Feature
This gauge is used for alarm and control functions. It consists of an indicating meter and contact mechanism and switches electric contacts by using the previously set pressure with the use of the built-in contacts other than the pressure indication function.
Spec
Size |
φ100
φ150 |
Shape of casing |
Standard case, Closed case
Type A/Type B/Type D |
Connecting thread |
φ100…G3/8 (G1/2)
φ150…G3/8 (G1/2) |
Material for the parts touching liquid |
(differs according to pressure)
*General Use
socket:C3604BD, YBSC3
bourdon tube:C2700T, SCM435,
SUS316
*Corrosion Resistant application
socket:SUS316
bourdon:SUS316 |
Pressure range |
Pressure gauge
0~40MPa(0~400kg/c㎡)
Vacuum gauge
-0.1~0MPa(76cmHg~0cmHg)
Compound gauge
-0.1~2.5MPa(76cmHg~25kg/c㎡) |
Contacts and electric rating |
Micro-switch(YEC-M)
(Electric rating:AC250V,5A or DC125V,0.4A)
Contact switch(YEC-C)
(Electric rating:AC100V,0.5A or AC200V,0.2A) |
Operating system |
Upper limit system
Lower limit system
Upper and lower limits system
Center connection system (only for micro-switch) |
|
Micro-switch
|
Contact switch
|
Operating system
|
|